1700 W Outdoor Enclosure Air Conditioner

1700 W outdoor enclosure air conditioner UP-AC-1700 is designed for sealed outdoor telecom and electrical cabinets that need active temperature control without bringing outside air into the enclosure. It combines closed-loop cooling, IP55 / IP65 protection and industrial communication options in a vertical cabinet-mount format.

UPCOM Model: UP-AC-1700
Cooling capacity: 1700 W L35/L35
Supply: 230 V

1700 W outdoor enclosure air conditioner for telecom cabinets

1700 W

Cooling capacity

IP55 / IP65

Protection

0 to +55 °C

Ambient

Modbus / EtherNet-IP

Communication

On this page

UP-AC-1700: Outdoor Cabinet Cooling

This model is a practical fit for higher-density telecom, edge and network cabinets with increased thermal load. The internal and external air circuits remain separated, helping keep the protected enclosure closed while heat is rejected to ambient air.

The controller is factory set to 34 °C with 4 °C hysteresis. Communication options include EtherNet/IP, ModBus TCP and ModBus RTU for compatible monitoring systems.

Technical Specifications

UPCOM modelUP-AC-1700
Cooling capacity (L35/L35)1700 W
Refrigerant / chargeR134a / 520 g
Factory thermostat setting34 °C
Hysteresis4 °C
External / internal airflow945 m³/h / 945 m³/h
Rated frequency50/60 Hz
Input voltage230 V
Power absorbed740 W
Running / starting current3.4 A / 4.4 A
Weight40 kg
Dimensions (H × W × D)955 × 400 × 255 mm
ConstructionGalvanized metal
MountingVertical cabinet mount
Protection (Ext./In)IP55 / IP65
Ambient operating range0 °C to +55 °C
CompressorDanfoss-Secop
FansEbmPapst
CommunicationEtherNet/IP, ModBus TCP, ModBus RTU

Technical values follow the current source-model manufacturer specification. Project conditions can affect actual thermal performance.

Typical Applications

  • Outdoor telecom and transmission cabinets
  • Network and edge-computing enclosures
  • CCTV, traffic and security-system cabinets
  • Industrial automation and control panels
  • UPS and power-electronics enclosures

Best fit: higher-density telecom, edge and network cabinets with increased thermal load.

When to Select 1700 W

Calculate equipment heat dissipation, solar gain and peak ambient temperature before selecting capacity. If the calculated load is close to 1700 W, review the next larger model rather than designing the system to operate continuously at its limit.

For quotation support, send enclosure dimensions, equipment heat load, maximum ambient temperature, target internal temperature, available voltage and quantity.

UP-AC-1700 FAQ

Is 1700 W the electrical power consumption?

No. 1700 W is the rated cooling capacity at L35/L35. The listed electrical power absorbed by this model is 740 W.

Can this unit be used in a sealed telecom cabinet?

Yes. It is intended for enclosure applications where the protected cabinet air should remain separated from the outdoor air circuit while heat is actively removed.

What information is needed for a quote?

Send cabinet dimensions, estimated heat load, site ambient range, target internal temperature, voltage, quantity and any communication requirement.

Request UP-AC-1700 for Your Project

UPCOM supplies enclosure cooling as a standalone unit or as part of a configured outdoor cabinet project.