Customer Portal REQUEST A QUOTE

Products › Rack cabinets › Outdoor rack cabinets

IP66 Floor-Standing Outdoor Rack Cabinets

These IP66 floor-standing outdoor rack cabinets house 19-inch switches, patch panels and telecom equipment. Choose 7U to 20U, a depth of 450 or 600 mm and single- or double-wall steel construction. All models include a 100 mm plinth.

12U floor-standing outdoor rack cabinet with a closed steel door and 100 mm plinth.
  • 7U to 20U
  • 600 × 450 / 600 × 600 mm
  • IP66 / IK10
  • 600 kg equipment load

19-inch rack with a floor plinth

Cables enter through the base. The front door locks, and the roof opens separately to reach the optional fan unit. The model tables list the external dimensions and empty weight of each enclosure.

Request a quote

Models and dimensions

Every height is available at both depths, with either wall construction. H is the overall cabinet height including the 100 mm plinth. The internal reference height h is shown in the dimensional drawings.

Rack heightExternal height HReference height h
7U586 mm361 mm
9U675 mm450 mm
12U808 mm583 mm
16U986 mm761 mm
20U1163 mm939 mm

Order codes and nominal cabinet weights

450 mm depth

Rack heightSingle wallDouble wall
7UUPC-EXT-7U450Z 27 kgUPC-EXT-7U450ZW 32 kg
9UUPC-EXT-9U450Z 29 kgUPC-EXT-9U450ZW 35 kg
12UUPC-EXT-12U450Z 32 kgUPC-EXT-12U450ZW 40 kg
16UUPC-EXT-16U450Z 36 kgUPC-EXT-16U450ZW 46 kg
20UUPC-EXT-20U450Z 40 kgUPC-EXT-20U450ZW 53 kg

600 mm depth

Rack heightSingle wallDouble wall
7UUPC-EXT-7U600Z 34 kgUPC-EXT-7U600ZW 40 kg
9UUPC-EXT-9U600Z 36 kgUPC-EXT-9U600ZW 42 kg
12UUPC-EXT-12U600Z 39 kgUPC-EXT-12U600ZW 48 kg
16UUPC-EXT-16U600Z 44 kgUPC-EXT-16U600ZW 55 kg
20UUPC-EXT-20U600Z 49 kgUPC-EXT-20U600ZW 63 kg

Specifications

ProtectionIP66 ingress protection; IK10 impact rating.
MountingStandard 100 mm plinth for floor mounting. The 19-inch rails carry U markings.
Material and finish1.5 mm steel outer shell, zirconium and zinc pretreatment, RAL 7035 light grey powder coating.
Wall constructionSingle wall or double wall with an additional 1 mm galvanized steel liner.
Equipment load rating600 kg equipment load. Nominal empty cabinet weights range from 27 to 63 kg.
Access and coolingLockable front door, bottom cable entry and hinged roof. Optional module with one or two fans.
Technical referencesThe model datasheets reference TS EN IEC 61587-1:2022, UL 2416 and RoHS.

Choosing a floor-standing outdoor rack cabinet

450 or 600 mm cabinet depth?

Use the longest installed device to select the depth. Include rear connectors, power leads and the bend radius of incoming fibre. The nominal 450 or 600 mm dimension is the external depth. Check rail position and door clearance against the drawings before specifying a switch or UPS.

Single wall or double wall?

Both versions use a 1.5 mm outer steel shell. The double-wall version adds a 1 mm galvanized inner liner and increases empty weight. At 12U and 600 mm depth, the single-wall cabinet weighs 39 kg and the double-wall cabinet 48 kg. Allow for that difference when planning delivery and installation.

How much room does a 19-inch outdoor rack need?

All models are 600 mm wide. A 7U cabinet is 586 mm high including the plinth. A 20U unit reaches 1,163 mm. Reserve space in front for the door, above for roof access and below the rack for the incoming cables. For active equipment, specify heat output and site conditions when requesting the optional one- or two-fan module.

Drawings and datasheet

The five-page family datasheet includes the size and weight table, an exploded view and separate dimension drawings for 450 mm and 600 mm depth.

Technical datasheet (PDF)

Select a cabinet for your quote

Your cabinet and accessory selections are included in the quote form and WhatsApp message. Add the quantity and delivery country to your enquiry.

Optional cabinet heaters and fan units

All four accessories fit every cabinet height and depth in this series, including single- and double-wall models. You can select a heater, a fan unit or both.

Order codeAccessory
F08IST-50W50 W cabinet heater with thermostat
F08IST-100W100 W cabinet heater with thermostat
UPC-F024F1OTOutdoor fan unit with one fan and digital thermostat
UPC-F024F2OTOutdoor fan unit with two fans and digital thermostat

Select a height, depth and wall construction to see the configuration.